*- TD Technology with thermal disconnect protection
- Compact design fi ts into DIN distribution panel boards and motor control centers
- 35 mm DIN rail mount – DIN 43 880 profile matches common circuit breakers
- Indication flags and voltage-free contacts provide remote status monitoring
- Separate plug and base design facilitates replacement of a failed surge module
- 100kA 8/20μs maximum surge rating provides protection suitable for sub-distribution panels and a long operational life
- Available in various operating voltages to suit most common power distribution systems
- CE, UL® 1449 Edition 3 Listed
Nominal System Voltage (Un) - 120 - 150 VAC
Max Continuous Operating Voltage (Uc) - 170 VAC
Stand-off Voltage - 2400 VAC
Frequency - 0 – 100 Hz
Short Circuit Current Rating (SCCR) - 200 kA
Back-Up Overcurrent Protection - 125 AgL, if supply > 100 A
Technology - TD technology with thermal disconnect
Max Discharge Current (Imax), - 100 kA 8/20 μs
Impulse Current, Iimp - 12.5 kA 10/350 μs
Nominal Discharge Current (In) - 50 kA 8/20 μs
Protection Modes - Single mode (L-G, L-N or N-G)
Voltage Protection Level (Up) - 400 V @ 3 kA | 1.0 kV @ 20 kA
Status - N/O, N/C Change-over contact, 250 V~/0.5 A, max 1.5 mm² (#14 AWG) terminals | Mechanical fl ag / remote contacts (R model only)
Dimensions H x D x W: mm (in) - 90 x 68 x 35 (3.54 x 2.68 x 1.38))
Module Width - 2 M
Weight: kg (lbs) - 0.24 (0.53)
Enclosure - DIN 43 880, UL94V-0 thermoplastic, IP 20 (NEMA-1)
Connection - 25 mm² (#4AWG) stranded | ≤35 mm² (#2AWG) solid
Mounting - 35 mm top hat DIN rail
Temperature - -40 to -80 °C (-40°F to 176°F)
Humidity - 0% to 90%
Approvals - CE, IEC® 61643-1, UL® 1449 Ed. 3 Recognized Component Type 2
Surge Rated to Meet - ANSI®/IEEE® C62.41.2 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs | IEC 61643-1 Class I and Class II| UL® 1449 Ed. 3 In 20 kA mode
Replacement MOV Module - TDS150M150
EAN-13 - 8711893046236