-Multi-stage protection with primary or combination
primary/secondary protectors
-10 pair protector
-Provides both L-L and L-PE protection modes for
comprehensive protection
-Simple installation into Krone® LSA disconnect block
-Data Line Terminator (DLT) available where screw
terminal connections are required
Part Number HSP10K230
Article Number 700860
Max Continuous Operating Voltage (Uc) 190 VDC
Max Discharge Current (Imax), L+L-PE 20 kA 8/20 μs
Rated Load Current (IL) 150 mA
Frequency 12 MHz Max
Transmission Rate 8 Mb/s
Protection Modes L-L
L-PE
Technology Multi-stage
Connection Type Krone® LSA-PLUS
Impedance Balance 55 dB Max
Insertion Loss .4 Db Max
Return Loss 20 dB Max
Loop Resistance 6.6 Ω
Temperature -20 to 60 °C
Enclosure Material UL® 94V-0 Thermoplastic
Depth (D) 21 mm
Height (H) 35 mm
Width (W) 125 mm
Unit Weight 0.02 kg
Certification Details UL® 497
Certifications A-Tick (Australia)
CE
C-Tick
cULus
Qualifoudre
Standard Packaging Quantity 1 pc
UPC 78285647505
EAN-13 9321098000545