*- Transient Discriminating (TD) Technology provides increased service life
- Modular design allows easy replacement of surge modules
- Built-in features include TD Technology, thermal protection and short circuit current fusing
- Compact NEMA®-4 enclosure design can be flush mounted or installed in a small space
- Status indication flag per mode, voltage presence LEDs, audible alarm and voltage-free contacts providing remote status monitoring
- 100 kA 8/20 μs maximum surge rating provides protection suitable for main-distribution panels and an extended operational life
Nominal System Voltage (Un) - 277/280 VAC
Distribution System - 3Ph 4W+G
Max Continuous Operating Voltage (Uc) - 320/550 VAC
Stand-off Voltage - 480/831 VAC
Frequency - 50 – 60 Hz
Short Circuit Current Rating (SCCR) - 200 kA
Nominal Discharge Current (In), IEC - 40 kA 8/20 μs
Nominal Discharge Current (In), UL - 20 kA 8/20 μs
Max Discharge Current (Imax), Per Phase - 100 kA 8/20 μs
Impulse Current (Iimp), Per Mode - 12.5 kA 10/350 μs | 25.0 kA 10/350 μs N-PE
Voltage Protection Rating (VPR) - 1,200 V @ 3 kA | 1,800 V @ 20 kA
Status Indication - LED | mechanical flag | Audible alarm
Surge Counter - No
Technology - TD technology with thermal disconnect | Over-current replaceable cartridge fusing
Lead Length - 762 mm
Lead Size - 5.26 mm²
Ground Lead Length - 914 mm
Temperature - -40 to 80 °C
Enclosure Material - Metal
Enclosure Rating - IP 65 | NEMA®-4
Mounting - 3/4” straight nipple
Depth (D) - 78 mm
Height (H) - 240 mm
Width (W) - 84 mm
Unit Weight - 1.41 kg
Certification Details - UL® 1449 Edition 4 Type 1/2, 10 kA Mode
Complies With - ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C
ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 2, 50 kA 8/20 μs
IEC® 61643-1 Class I, Class II
Replacement Module - TDS150M277 | SGD125M
Certifications - CE | C-Tick| Qualifoudre | UL
Standard Packaging Quantity - 1 pc
UPC - 78285659382
EAN-13 - 8711893097030