*- High-performance protection incorporating Spark Gap and Transient Discriminating (TD) technologies
- High surge rating ideal for exposed critical service entrance applications
- Reduces let-through voltages and rate-of-voltage rise (dv/dt) and helps provide optimum protection for electronic equipment
- Extreme reliability and simplified design with direct connection from input to output
- Comprehensive front panel status and internal diagnostic LEDs
Nominal System Voltage (Un) - 220/380 - 240/415 VAC
Distribution System - 3Ph Y 4W+G
System Compatibility - TN-C | TN-C-S | TN-S | TT
Rated Load Current (IL) - 63 A
Frequency - 50 – 60 Hz
Short Circuit Current Rating (SCCR) - 43 kA
Heat Dissipation - 34 W
Rate of Voltage Rise (dV/dt) - 5 V/µs Max
Filtering - -40 dB @ 100 kHz
Input Connection - 10 - 35 mm²
Output Connection - 10 - 35 mm²
Protection Modes - All modes protected
Technology - Spark Gap | In-line series low pass sine wave filter | TD technology with thermal disconnect (50 kA 8/20us secondary stage)
Enclosure Material - Metal
Enclosure Rating - IP 65
Mounting - Wall mount
Status Indication - Front panel LED | Internal diagnostic primary and secondary protection LEDs | Change-over contact (Form C dry), 250 VAC/30 VDC/5 A, 4 kV isolation
Depth (D) - 200 mm
Height (H) - 500 mm
Width (W) - 400 mm
Unit Weight - 17.7 kg
Complies With - IEC® 61643-11 Class I, Class II | ANSI®/IEEE® C62.41.2-2002 Cat A, Cat B, Cat C | ANSI®/IEEE® C62.41.2-2002 Scenario II, Exposure 3, 100 kA 8/20 μs, 10 kA 10/350 μs
Certifications - CE | Qualifoudre
Standard Packaging Quantity - 1 pc
UPC - 78285691539
EAN-13 - 0782856915393